1. Product Features
 
DZ518 series motor protecting breaker adopts the design of module,It has beautifulshape,small value,complete range of function and reliable performance.DZ518 series is conformity with IEC60947.2, IEC60947-4.1, andEN60947-1 standards,Switch an contactor can make up the starting of the motor The prection grade of the case of DZ518 series can reach IP55. DZ518 series has three types of products. DZ518 series is button-controlling motor with hot magnetic protecting breaker,DZ518 series is switch-shifting controlling motor with hot mangnetic protecing breaker,DZ518 serrues is switch-shifting controlling motor with magnetc protecting breaker.
 
2. Specification
 
DZ518(ME)
DZ518
DZ518
M01C
0.1-0.16
RS01C
0.1-0.16
M02C
0.16-0.25
RS02C
0.16-0.25
M03C
0.25-0.40
RS03C
0.25-0.40
LS03
0.25-0.40
M04C
0.40-0.63
RS04C
0.40-0.63
LS04
0.40-0.63
MO5C
0.63-1
RS05C
0.63-1
LS05
0.63-1
MO6C
1-1.6
RS06C
1-1.6
LS06
1-1.6
MO7C
1.6-2.5
RS07C
1.6-2.5
LS07
1.6-2.5
MO8C
2.5-4
RS08C
2.5-4
LS08
2.5-4
M10C
4-6.3
RS10C
4-6.3
LS10
4-6.3
M14C
6-10
RS14C
6-10
LS14
6-10
M16C
9-14
RS16C
9-14
LS16
9-14
M18C
10-16
RS18C
10-16
LS18
10-16
M20C
13-18
RS20C
13-18
LS20
13-18
M21C
17-23
RS21C
17-23
LS21
17-23
M22C
20-25
RS22C
20-25
LS22
20-25
M32C
24-32
RS32C
24-32
 
The rated power of three-phase electromtor controlled by breaker(GV2 motor circuit breaker)
 
Adjusting range of rated current (A)
Standard power of three-phase electromotor( KW) AC-3
50/60Hz
230/240V
400V
415V
440V
500V
690V
0.1-0.16
-
-
-
-
-
-
0.16-0.25
-
-
-
-
-
-
0.25-0.4
-
-
-
-
-
-
0.4-0.63
-
-
-
-
-
0.37
0.63-1
-
-
-
0.37
0.37
0.55
1-1.6
-
0.37
-
0.55
0.75
1.1
1.6-2.5
-
0.75
0.75
1.1
1.1
1.5
2.5-4
0.37
1.5
1.5
1.5
2.2
3
4-6.3
0.75
2.2
2.2
3
3.7
4
6-10
1.1
4
4
4
5.5
7.5
9-14
2.2
5.5
5.5
7.5
7.8
9
13-18
3
7.5
9
9
9
11
17-23
4
11
11
11
11
15
20-25
5.5
11
11
11
11
18.5
24-32
5.5
15
15
15
18.5
23
 
 
3. AIR SWITCH OF THE MOTOR
 
The disjointing current commuting value of breaker in instantmagnetic field
 
Rated current In(A)
Adjusting range(A)
Disjointing current(A)
>0.16
0.1-0.16
1.5
0.25
0.16-0.25
2.4
0.4
0.25-0.4
5
0.63
0.4-0.63
8
1
0.63-1
13
1.6
1-1.6
22.5
2.5
1.6-2.5
33.5
4
2.5-4
51
6.3
4-6.3
8
10
6-10
138
14
9-14
<170
18
13-18
223
23
17-23
327
25
20-25
327
32
24-32
416
 
 
4. Contacts of accessories
 
Names of accessories Code The types of comtacts Installation place
Instantaneous
auxiliary contacts
SE1 constant-open or constant 1 closed The foront of breaker (1PCS)
SE11 constant-open or constant 1 closed
SE20 two constant open
SN11 constant-open or constant 1 closed the left of breaker (4PCS)
SN20 2constant open
instantaneous
auxiliary contacts
+
Instantaneous
auxiliary contacts
SD1010 constant-open trouble contant-open
SD1001 contant-closed
SD0110 constant-closed trouble contant-open
SD0101 contant-closed
Short circuit contacts SM11 constant-open or constant 1 closed
 
 

5. Electric disjointing

 
Names of accessories
Voltage
Code
Installation place
Memo
Lack-voltage disjointing
110-127V 50Hz
SU115
The right of breaker
(1PCS)
110-127V 50Hz
SU225
110-127V 50Hz
SU385
Division disjointing
110-127V 50Hz
SS115
110-127V 50Hz
SS225
110-127V 50Hz
SS385
Be used to the release
of low voltage
110-127V 50Hz
SX115
110-127V 50Hz
SX225
110-127V 50Hz
SX385
 
 

6. The protective case of breaker

 
Names of accessories The protection degree of shell Code Memo
External installation shell 1P 41 MC01
-
1P 55 MC02
1P 55 MC03
 
 

 

 